Application
To be laid directly in ground, outdoors, indoors and in cable ducts.
Used for infrastruction, high building foundations, power distribution and connection.
Construction
1 stranded annealed copper
2 XLPE insulation
3 PVC innnear sheath
4 .Galvanized Steel Wire Armour
5. PVC outer sheath
Standards
IEC 60502, 60228, 60332, 60331
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Certificate: CE, Gost, KEMA
Technical data
Rated voltage: 0.6 / 1 kV
Max. Conductor Temp.: normal (90ºC), short circuit no more than 5 s (160ºC when section-area below 300mm2, 140ºC when section-area above 300mm2)
Min. Ambient Temp.:The cable shall be pre heated if the ambient temperature is below 0ºC
Min. Bending Radius: 15 *(cable O.D)