Models and specifications of fire protection wires and cables

2025-08-28 Leave a message

Fire cable specifications vary depending on their use and function, primarily categorized as automatic fire alarm system cables, fire linkage control cables, fire broadcast cables, and fire telephone cables. The following are common fire cable specifications and their application scenarios:


1. Automatic fire alarm system cables


Alarm bus (signal cable)


ZR-RVS-2×1.0mm² / 2×1.5mm² (red and blue twisted pair, red is positive, blue is negative)


NH-RVS-2×1.0mm² (fire-resistant, for trunk and branch lines)


Power cable (DC24V)


ZR-BV-2×1.5mm² / 2×2.5mm² (1.5mm² for flat surfaces, 2.5mm² for vertical shafts)


NH-BV-2×2.5mm² (fire-resistant, for trunk lines)


2. Fire Alarm Control Cable


Multi-wire Control Cable (Hard-wire Control)


WDZBN-KYJV-8×1.5mm² (For key equipment such as smoke exhaust fans and fire pumps)


ZR-KVV-5×1.0mm² / 1.5mm² (Multi-wire Reel Control Cable)


Fire Hydrant Button Control Cable


ZR-BV-1.5mm² (Black and White) (Direct Pump Control Cable)


3. Fire Alarm Cable


ZR-RVS-2×1.0mm² / 2×1.5mm² (Yellow-green Twisted Pair)


NH-RVS-2×1.5mm² (Fire-resistant)


4. Fire Telephone Cable


ZR-RVVP-2×1.0mm² / 2×1.5mm² (Shielded Flexible Cable)


NH-RVVP-2×2.5mm² (Trunk Line), 2× 1.5mm² (branch line)


5. Other Fire Protection Cables


Fan Control Cable


ZR.BV-1.5mm² (yellow, green, and red)


Fire Display Panel Signal Cable


ZR-RVS-2×1.5mm²6


Gas Fire Extinguishing Control Cable


ZR-BV-4×1.5mm² (start/stop button), ZR-BV-2×1.5mm² (gas release indicator light)


6. Fire-Resistant Cable (Fire Protection Power Distribution Line)


BTTZ (Copper core, copper sheathed, magnesium oxide mineral insulated cable, high temperature resistant and fireproof)


BTTRZ (RTTZ) (Flexible mineral insulated fireproof cable)


NG-A (BTLY) (Aluminum sheathed, flexible, isolated fireproof cable)


ZR-YJV, ZR-VV, ZR-KVV (Flame-retardant power cables, suitable for fire protection power distribution)