PVC insulated and sheathed control cables

2025-09-02 Leave a message

1. Product Application: PVC insulated and sheathed control cables are suitable for use in control, monitoring, and protection circuits with an AC rated voltage U0/U of 450/750V or less, as control wiring between electrical equipment.


2. Implementation Standard: GB/T9330-2008 "Plastic Insulated Control Cables"

3. Usage Characteristics


3.1 The long-term permissible operating temperature of the cable conductor is 70°C. During a short circuit (maximum duration not exceeding 5s), the maximum temperature of the cable conductor shall not exceed 160°C.


3.2 The installation and laying temperature shall not be lower than 0°C.


3.3 Recommended Bend Radius: For unarmored cables, the bending radius should be no less than 6 times the cable's outer diameter; for cables with armor or copper tape shielding, the bending radius should be no less than 12 times the cable's outer diameter; for shielded flexible cables, the bending radius should be no less than 6 times the cable's outer diameter.


4. Cable Models and Names


KVV Copper-core PVC insulated, PVC sheathed, braided-shielded control cable


KVVP Copper-core PVC insulated, PVC sheathed, braided-shielded control cable


KVVP2 Copper-core PVC insulated, PVC sheathed, copper-tape-shielded control cable


KVVP3 Copper-core PVC insulated, PE sheathed, aluminum-plastic composite-tape-shielded control cable


KVV22 Copper-core PVC insulated, PVC sheathed, steel-tape-armored control cable


KVV32 Copper-core PVC insulated, PVC sheathed, fine-wire-armored control cable


KVVP2-22 Copper-core PVC insulated, PE sheathed, copper-tape-shielded, steel-tape-armored control cable


KVVR Copper core PVC insulated PVC sheathed flexible control cable

KVVRP Copper core PVC insulated PVC sheathed braided shielded flexible control cable

Note: The model and name of flame-retardant and fire-resistant cables shall comply with GB/T 19666. For standard cable models, add ZA, ZB, ZC, ZD, or N before the model number.