Oxygen-Barrier Flame-Retardant Fire-Resistant Power Cable
Scope of Application
This product is suitable for power lines with an AC rated voltage of 0.6/1 kV and below, for power transmission and distribution.
Specifications
1. Rated voltage Uo/U is 0.6/1 kV.
2. Permissible Long-Term Operating Temperature of Cable Conductor:
The long-term operating temperature of PVC-insulated oxygen-barrier cable shall not exceed 70°C;
The long-term operating temperature of XLPE-insulated oxygen-barrier cable shall not exceed 90°C.
3. The cable laying temperature should not be lower than 0°C. If the cable is laid below 0°C, it must be preheated.
4. Bending Radius:
Permissible bending radius for single-core cable: 20 (D + d) ± 5%
Permissible bending radius for multi-core cable: 15 (D + d) ± 5%
D = Actual outer diameter of cable specimen (mm)
d = Actual conductor diameter (mm)