Structure
1. Conductor - Plain annealed class 2 stranded (compacted) copper
2. Insulation - Cross linked polyethylene (XLPE)
3. Filler - Non-hygroscopic material
4. Binder tape - Non-hygroscopic material tape
5. Inner sheath - Polyvinyl chloride compound (PVC)
6. Armor - Galvanized steel wires
7. Binder tape - Non-hygroscopic material tape
8. Outer sheath - Polyvinyl chloride compound (PVC)
Application
To be used for main power supply such as in low voltage distribution power networks, indoor and outdoor areas. It can be installed in ducts, in dry or wet locations, recommended for direct burial where require higher electrical and mechanical protection.
Temperature characteristics
Conductor operating temperature: -15ºC~90ºC
Min. temperatrue laying condition: 0ºC
Conductor emergency operating temperature: 105ºC
Conductor short-circuit operating temperature (5s): 250ºC
Electrical Characteristics
Rated voltage: 0.6/1 (1.2) kV
High voltage test: 3.5kV / 5min
Color
Insulation: According to customer requirements
Outer sheath: Black or according to customer requirements
Standard
Cable design: IEC 60502-1 or AS/ZNS 5000.1
Conductor: IEC 60228 or AS/ZNS 1125