6181y Double Insulated Cable

6181y Double Insulated Cable

Cable Approvals:
Cable approved to BS6004

Key Applications:
Fixed installation in dry or damp premises on walls, boards or trays, in channels or embedded in plaster.

Conductor: 
Plain annealed copper solid (1.0 - 2.5mm²) or stranded (4.0 - 35.0mm²)
circular conductor complying with BS EN 60228 Class 1 or Class 2

Insulation:
PVC Insulation complying with BS EN 50363-3 Type Tl1

Core Identification:
red,black,blue,brown

Sheath:
PVC Sheath complying with BS7655 Type 6
Normally grey but others available on request

Voltage Rating:
300/500 volts, 120mm rated at 600/1000 volts

Temperature Rating:
-15°C to +70°C

Minimum Bending Radius:
Up to 10mm2  - 3 x overall diameter
Above 10mm2  - 4 x overall diameter

Should not be installed at temperatures below 0°C or above +60°C.